FAQ / Troubleshooting
My Module doesn't seem to be outputting anything.
Confirm that your CAN bus is properly terminated and that all nodes are configured for the right bus speed. In
addition, any receiving devices/nodes must be specifically configured to receive as the Module is configured to
transmit; specifically, the CAN ID, bus speed, and number of ID bits.
The temperatures that my module is outputting don't make sense.
Thermocouple wires have polarity meaning there is a positive (+) and negative (-) wire. Please ensure that the
polarity is correct from the sensor, through any extensions, and to the correct terminal on the Module. The polarity
is marked on the top of the enclosure of the Module. All sensor wiring and/or extensions must be constructed of the
proper K-type alloy wire. The Module will output a temperature of "
3276.7 degC"
when a channel does not have a
sensor plugged in.
Can I use the Module with my AEM CAN Gauge
No, the CAN Sensor Module is only compatible with CD-series dash displays, AEM AQ-1, AEM Infinity ECUs and
other third-party devices at this time.
Where can I find AEM .dbc files?
AEM dbc files are available via the AEM Forum and within the AEM CD-series dash display software installer.
Please visit
for more information and downloads.
For support, contact AEM Technical Support at 1-800-423-0046 or
.
AEMnet (CAN Bus) Output
WHITE WIRE = / CANH
GREEN WIRE = AEMnet- / CANL
CAN DBC definition files are available at
Bus Termination
All AEMnet/CAN networks must be terminated to have
an equivalent of approximately 60 Ohms of resistance.
Generally, this means a 120 Ohm resistor connected in
parallel to /AEMnet- (or CANH/CANL) at both
physical ends of the bus run.
bit rate
Selectable via Jumper
kb/sec
format
Selectable via Jumper
bit ID
terminating resistor
NONE
endianness
big / Motorola
DLC
8
Unit 1:
0x0000BA00 (29) / 0x5A0 (11) at
10Hz
Unit 2:
0x0000BB00 (29) / 0x5B0 (11) at 10Hz
Byte
Label
Data Type
Scaling
Offset
Range
0
Thermocouple1
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
1
2
Thermocouple2
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
3
4
Thermocouple3
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
5
6
Thermocouple4
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
7
Unit 1:
0x0000BA01 (29) / 0x5A1 (11) at
10Hz
Unit 2:
0x0000BB01 (29) / 0x5B1 (11) at 10Hz
Byte
Label
Data Type
Scaling
Offset
Range
0
Thermocouple5
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
1
2
Thermocouple6
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
3
4
Thermocouple7
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
5
6
Thermocouple8
16 bit signed
0.1 degC/bit
0
-3276.8 to +3276.7 degC
Содержание CD-5 Carbon
Страница 12: ...12 Dash Mechanical and Mounting CD 7 Mechanical ...
Страница 13: ...13 CD 5 Mechanical ...
Страница 14: ...14 CD 7F Mechanical ...
Страница 15: ...15 CD 5F Mechanical ...
Страница 16: ...16 Drill Template Drill template prints to scale ...
Страница 17: ...17 Dash Harness and Basic Wiring ...
Страница 18: ...18 Optional OBDII and Power Cable Kits ...
Страница 30: ...30 Create a new output channel using the new function Assign the new output to an item on the display ...
Страница 31: ...31 System Schematic ...
Страница 39: ...39 IMAGE NOT TO SCALE ...
Страница 41: ...41 System Schematic ...
Страница 51: ...51 CAN Transmit Rate Unit 1 50 Hz CAN Transmit Rate Unit 2 25 Hz ...
Страница 58: ...58 ID Type User Configurable 11 29 bits Termination None Ohm DLC 8 Bytes ...
Страница 64: ...64 ...
Страница 65: ...65 ...
Страница 66: ...66 ...
Страница 67: ...67 ...