Installation
28
UPS 30-300kVA User Manual
PE
Cables crimped OT terminal
M6
4.9Nm
120kVA
Mains input
Cables crimped OT terminal
M10
15Nm
Bypass Input
Cables crimped OT terminal
M10
15Nm
Battery Input
Cables crimped OT terminal
M10
15Nm
Output
Cables crimped OT terminal
M10
15Nm
PE
Cables crimped OT terminal
M10
15Nm
180kVA
Mains input
Cables crimped OT terminal
M12
28Nm
Bypass Input
Cables crimped OT terminal
M12
28Nm
Battery Input
Cables crimped OT terminal
M12
28Nm
Output
Cables crimped OT terminal
M12
28Nm
PE
Cables crimped OT terminal
M12
28Nm
300kVA
Mains input
Cables crimped OT terminal
M16
96Nm
Bypass Input
Cables crimped OT terminal
M16
96Nm
Battery Input
Cables crimped OT terminal
M16
96Nm
Output
Cables crimped OT terminal
M16
96Nm
PE
Cables crimped OT terminal
M16
96Nm
2.6.3 Circuit Breaker
The circuit breakers (CB) for the system are recommended inTable 2-4.
Table 2-4 Recommended CB
Installed
position
60kVA
120kVA
180kVA
300kVA
Main input
CB
225A/3P
400A/3P
630A/3P
800A/3P
Bypass
input CB
225A/3P
400A/3P
630A/3P
800A/3P
Output CB
225A/3P
400A/3P
630A/3P
800A/3P
Manual
225A/3P
400A/3P
630A/3P
800A/3P
Bypass
CB
Battery CB
300A,
630A,
630A,
250Vdc
1250A,
250Vdc
250Vdc
250Vdc
Attention
The CB with RCD (Residual Current Device) is not suggested for the system.