UPS 30-300kVA User Manual
Installation
19
(d) Dimensions
of 210KVA ~300kVA (unit: mm)
Figure2-2Dimensions
Ensure that the floor or installation support can bear the weight of the UPS, batteries, and battery
racks. The weight of batteries and battery racks depends on the site requirements. The weight for
the UPS cabinet is shown in Table 2-1.
Table 2-1 weight for the UPS
Capacity
Weight
30KVA
165 Kg
60KVA
210 Kg
90KVA
305 Kg
120KVA
350 Kg
150KVA
445 Kg
180KVA
490 Kg
210KVA
765 Kg
240KVA
810 Kg
270KVA
855 Kg
300KVA
900 Kg
2.2 Unloading and Unpacking
2.2.1
Moving and Unpacking of the Cabinet
The steps to move and unpack the cabinet are as follows
: