UPS 30-300kVA User Manual
Operator Control and Display Panel
47
Submenu
Name
Contents
Meaning
BATTERY
Battery Capacity
Setting of the AH of the battery
Float Charge Voltage/Cell
Setting the floating Voltage for battery cell
(
2V
)
Boost Charge Voltage/Cell
Setting the boost Voltage for battery cell
(
2V
)
EOD(End of
discharge)
Voltage/Cell,@0.6C
Current
EOD voltage for cell battery,@0.6C current
EOD(End of
charge)
Voltage/Cell,@0.15C
Current
EOD voltage for cell battery,@0.15C
current
Charge Current Percent
Limit
Charge current (percentage of the rated
current)
Battery Temperature
Compensate
Coefficient for battery temperature
compensation
Boost Charge Time Limit
Setting boost charging time
Auto Boost Period
Setting the auto boost period
Auto Maintenance
Discharge Period
Setting the period for auto maintenance
discharge
SERVICE
System Mode
Setting the system mode: Single , parallel,
Single ECO, parallel ECO,LBS, parallel
LBS
RATE
Configure the rated
Parameter
For the factory use
CONFIGURE
Configure the system
For the factory use
Note
�
Users have various permissions to the configuration of the Setting :( a) for the Date &Time, LANGUAGE
and COMM, user can set on their own without password. (b)For the USER, a one-level password is needed
and the setting must be done by commissioning engineer (c) For the Battery and SERVICE, a Two-level
password is needed and it is set by the after-service personal. (d)For the RATE and CONFIGURE, a
Three-level password is needed and it is set only by the factory.
�
The “C” stands for Ampere number. For instance, if the battery
is 100AH
,
then C=100A.
Warning
Ensure the number of the battery, set via the menu or the monitoring software, is completely equal
to the real installed number. Otherwise it will cause serious damage to the batteries or the
equipment.
3.2.4 Log
Touch the icon
, (At the bottom of the screen), and the system enters the interface of the
Log, as it is shown in Figure3-9.The log is listed in reverse chronological order(i.e. the first on the
screen with #1 is the most new), which displays the events ,warnings and faults information and