Operator Control and Display Panel
54
UPS 30-300kVA User Manual
Temp.
86
Bypass Fan
Expired
Working life of bypass fans is expired, and it’s recommended that
the fans are replaced with new fans. It must be activated via
software.
87
Capacitor Expired
Working life of capacitors is expired, and it’s recommended that the
capacitors are replaced with new capacitors. It must be activated via
software.
88
Fan Expired
Working life of power modules’ fans is expired, and it’s
recommended that the fans are replaced with new fans. It must be
activated via software.
89
INV IGBT Driver
Block
Inverter IGBTs are shutdown.
Please check if power modules are inserted in cabinet correctly.
Please check if fuses between rectifier and inverter are broken.
90
Battery Expired
Working life of batteries is expired, and it’s recommended that the
batteries are replaced with new batteries. It must be activated via
software.
91
Bypass CAN Fail
The CAN bus between bypass module and cabinet is abnormal.
92
Dust Filter Expired
Dust filter need to be clear or replaced with a new one
102
Wave Trigger
Waveform has been saved while UPS fail
103
Bypass CAN Fail
Bypass and cabinet communicate with each other via CAN bus.
Check
If connector or signal cable is abnormal.
If monitoring board is abnormal.
105
Firmware Error
Manufacturer used only.
106
System Setting
Error
Manufacturer used only.
107
Bypass Over
Temp.
Bypass module is over temperature. Please check
If bypass load is overload
If ambient temperature is over 40°C
If bypass SCRs are assembled correctly
If bypass fans are normal
108
Module ID
Duplicate
At least two modules are set as same ID on the power connector
board, please set the ID as correct sequence
Note
Different colors of the words represent different level of events:
(a)Green, an event occurs
;
(b)Grey, the event occurs then clears
;
(c)Yellow, warning occurs
;
(d) Red, faults happen.
3.2.5 Operate
Touch the icon
(At the bottom of the screen), and the system enters the page of the
“Operate”, as it is shown in Figure3-10.