The events, which are captured by the Thyro-AX, are shown on the
touch display in abbreviated form in a list. They correspond with the full
forms in their meaning and can be discerned using the table above.
6.8.2 FAULT SIGNALING RELAY K1
NOTE
DEFAULT SETTING
The function explained here is described in its default setting.
This setting can be altered with the control panel, with a bus module,
or with the Thyro-Tool AX.
FIG. 7 CONTACT
ASSIGNMENT
FAULT
SIGNALING
RELAY K1
DESCRIPTION
THYRO-TOOL AX
MESSAGE
DISPLAY
RELAY** PULSE INHIBIT
DATA
OF STATUS
MESSAGE
ON DISPLAY
LIGHTING RED
LOGGER
PULSES ARE SWITCHED ON
IMPULSE ON
PULSE ON
-
PULSE OFF AT
PULSE SWITCH OFF
PULOFFT
X
-
TERMINAL X2.1-X2.2
TERMINAL
PULSE OF AT
PULSE SWITCH OFF
PULOFFHW
X
-
X
HARDWARE (ERROR)
HARDWARE ERROR
PULSE OF AT SOFTWARE
PULSE SWITCH OFF
PULOFFEV
X
-
X
(CONFIGURABLE) EVENT
PULSE OF EXTERNAL
PULSE SWITCH OFF
PULOFFEX
X
-
EXTERN
LEFT ROTATING FIELD
LEFT ROTATING FIELD
LEFTROTF
X
X
X
(MESSAGE ONLY)
U LIMIT
U LIMIT
U LIMIT
X
I LIMIT
I LIMIT
I LIMIT
X
P LIMIT
P LIMIT
P LIMIT
X
IPEAK LIMIT
I PEAK LIMIT
IPEAKLIMIT
X
ALPHA IS RESTRICTED
ALPHA RESTRICTED
ALPHA
TS IS RESTRICTED
SWITCH ON TIME
TS
RESTRICTED
MAXIMUM CONTROLLER
MAXIMUM OUTPUT
MAXCONTROL
OUTPUT IS REACHED
REACHED
SETPOINT OF BUSMODULE
BUSMODULE
BUS SETP
IS ACTIVE
SETPOINT ACTIVE
BUSMODULE IS CONNECTED
BUSMODULE
BUS CONN
CONNECTED
CLOCK IST NOT SET
CLOCK NOT SET
NO CLOCK
POWER UNITS ARE HIGHER
POWER UNIT
DIFF PPART
X
THAN TYPE
DIFFERENT
POWER CONTROLLER IS OK
POWER CONTROLLER
THYRO OK
-
OK
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
DESCRIPTION
THYRO-TOOL AX
MESSAGE
DISPLAY
RELAY** PULSE INHIBIT
DATA
OF MONITORING
MESSAGE
ON DISPLAY
LIGHTING RED
LOGGER
U
MAINS
MIN
U MAIN < MINIMUM
UN MIN
X
U
MAINS
MAX
U MAIN > MAXIMUM
UN MAX
X
U
LOAD
MIN
U < MINIMUM
UL MIN
X
U
LOAD
MAX
U > MAXIMUM
UL MAX
X
I
LOAD
MIN
I < MINIMUM
IL MIN
X
I
LOAD
MAX
I > MAXIMUM
IL MAX
X
P
LOAD
MIN
P < MINIMUM
PL MIN
X
P
LOAD
MAX
P > MAXIMUM
PL MAX
X
R
LOAD
MIN
R < MINIMUM
RL MIN
X
R
LOAD
MAX
R > MAXIMUM
RL MAX
X
X
X
I
PEAK
MAX
I PEAK > MAXIMUM
I_PEAK MAX
X
MAX. TEMP. OF HEAT SINK
TEMPERATURE UNIT >
T_HEAT MAX
X
X
X
MAXIMUM
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
TAB. 5 STATUS
TAB. 6 MONITORING