CONNECTION DATA OF THE POWER CONNECTION
Grounding screw/bolt for protective conductor connection to the heat
sink. The grounding also serves EMC means (Y - capacitor 4.7 nF).
CONNECTION GROUNDING CONDUCTOR
L1, T1, L2, T2,
SCREW
CROSS-
L3,
T3
SECTION
16 / 30 A
lug / M4
lug / M4
maximum 6 mm
2
45 A*
M 6
M 6 maximum 50 mm
2
60* / 100 A*
M 6
M 6 maximum 50 mm
2
130 / 170 / 230 A M 8
M 10
95 / 120 mm
2
240 / 280 A
M 10
M 10
150 / 185 mm
2
350 A
M 10
M 10
185 mm
2
495 A
M 10
M 10
Cu 48x3; 2xø11
650 A
M 10
M 10
Cu 48x3; 2xø11
1000 A
M12
M12
Cu 60x10; 2xø14
1400 A
M12
M12
Cu 60x10; 2xø14
1500 A
M12
M12
Cu 60x10; 2xø14
TAB. 13 CONNECTION DATA OF THE POWER CONNECTION
With UL applications only use 60 °C or 60 °C/75 °C copper conductors
(with the exception of control cables).
* With UL applications only use 75 °C copper conductors (with the
exception of control cables).
SCREW
MIN. VALUE
[NM]
NOM.
VALUE
[NM]
MAX.
VALUE
[NM]
POWER
CONNECTION
GROUND
CONNECTION
FUSE
CONTROL
WIRE
TYPE IN [A]
M2
0.2
0.25
0.3
Phoenix
terminals
M3
0.6
0.75
0.9
16;30
Phoenix
terminals
M4
1.0
1.2
1.4
16;30
M5
1.7
2.0
2.3
16;30
M6
2.6
3.0
3.5
45;60;100
45;60;100
45;60;100
M8
5.1
6.0
6.9
130;170;230 130;170;230;
240;280;350
130;170;230;
M10
8.5
10.0
11.5
240;280;350
240;280;350
M12
13.2
15.5
17.8
1 Pound-Force Inch = 0.112985 Newton Meter
Tightening torques for electric connections in Nm
Tightening torques for electric connections in pound inches
SCREW
MIN. VALUE
[POUND
INCHES]
NOM.
VALUE
[POUND
INCHES]
MAX.
VALUE
[POUND
INCHES]
POWER
CONNECTION
GROUND
CONNECTION
FUSE
CONTROL
WIRE
TYPE IN [A]
M2
1.9
2.2
2.5
Phoenix
terminals
M3
5.6
6.6
7.6
16;30
Phoenix
terminals
M4
9.0
10.6
12.2
16;30
M5
15.0
17.7
20.4
16;30
M6
22.6
26.6
30.5
45;60;100
45;60;100
45;60;100
M8
45.1
53.1
61.1
130;170;230 130;170;230;
240;280;350
130;170;230;
M10
75.2
88.5
101.8
240;280;350
240;280;350
M12
116.6
137.2
157.8
TAB. 14 TIGHTENING TORQUES