7.8 MENU STRUCTURE
MENU
SUBMENU
DEFAULT VALUE
REMARKS
ActVal
Main menu of the current value overview. Also appears
automatically after a period of 30 sec. of not changing
Event
List of all current active messages (events).
OK has the function of acknowledging the relevant message.
Settings
Operating
1A: TAKT, 2A: TAKT,
3A: VAR
Operating mode, operating of thyristors
Regulator
U x U
Current, voltage or power based control.
Limit
Type values of the
device
Maximum value for current, voltage and power.
Takt
(for operating mode
TAKT)
CyclTime
50 per
Cycle period
Alpha1st
1A: 60° el, 2A: 90° el,
3A: 90° el
Phase angle of the 1st half wave
SST
6 per
Soft-start time
Switch
(for operating mode
SWITCH)
Alpha1st
1A: 60° el, 2A: 90° el,
3A: 90° el
Phase angle of the 1st half wave
SST
6 per
Soft-start time
Monitoring
R_Max = (type voltage
* 2)/type current
R_Max for load monitoring
AS 1
0-20mA
Signal for analog setpoint 1
AS 2
0-20mA
Signal for analog setpoint 2
AO 1
Range
0-20mA
Dimensions for analog output 1
Source
Average
Source for measurment (crucial if Value or ValuePh will be
displayed).
Value
OFF
Output of general values (source must be set to general).
ValuePh
AO 1: U, AO 2: I, AO
3: OFF
Output of phase related values (source must be set to L1, L2,
L3, Min, Max or average).
ScaleMax
Full scale value
AO 2
(like AO 1)
AO 3
(like AO 1)
ReadSet
Overview of all device parameters.
Code
Authorization code for parameter changes and digital
setpoint entry at display.
Save
Save the current parameters in EEPROM. This is shown
automatically after a modification, when the menu is
acknowledged.
Load
Load EEPROM
Load customer parameters from EEPROM.
Load Factory Set.
Load default settings.
TeachIn
Start the load measuring for automatic load failure detection.
EasyStart
Start the quick configuration of the device by basic
parameters.
Eth.Set.
DHCP/Static
DHCP
Method of assigning IP address.
IP Adr
192.168.0.100
Read the assigned IP address or write the static one.
Submask
255.255.255.0
Subnet mask of network.
Gateway
192.168.0.254
Gateway of network.
1. DNS
194.25.2.129
IP of domain name server 1.
2. DNS
130.146.25.194
IP of domain name server 2.
USB Menu
Read and write the parameters via USB flash drive.
TAB. 9 MENU STRUCTURE THYRO-AX
7.9 THYRO-TOOL AX
The software Thyro-Tool AX (hereafter referred to as Tool) is suitable
for parameterization and visualization of connected devices of series
Thyro-AX. Parameter and line charts can be saved. During installation
a server (Windows service: ThyroWindowsService) and client will be
installed, which will be started parallel in the simplest case. There is an
option to access device, which are connected to a computer, by using
remote maintenance on another computer.
FIG. 9 CONNECTION TO LOCAL INSTALLED SERVER
The left side of the window offers an own explorer for open files and
directly connected devices. On the right side, tabs are shown for each
subsection which has been selected by double clicking on it. There are
3 different options to switch between the open windows:
- Double click on explorer (like opening for the first time)
- Select tab
- Drop-down menu (Overview with icons)
FIG. 10
SEVERAL OPEN TABS
The field with status messages can be transferred as an external win-
dow back and forth for an improved overview. Therefore stretch out the