TAB. 8 ACKNOWLEDGMENT
DESCRIPTION OF
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
FAULT
MESSAGE
ON DISPLAY
LCD DISPLAY
THYRISTOR SHORT CIRCUIT
THYRISTOR SHORT
THYRISTOR
X
CIRCUIT
U-MEASURING RANGE
U MEASURING
U RANGE
X
IS EXCEEDED
RANGE EXCEEDED
I-MEASURING RANGE
I MEASURING
I RANGE
X
IS EXCEEDED
RANGE EXCEEDED
NEGATIVE POWER
NEGATIVE POWER
NEG POWER
X
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
DESCRIPTION OF
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
STATUS
MESSAGE
ON DISPLAY
LCD DISPLAY
U LIMIT
U LIMIT
U LIMIT
X
I LIMIT
I LIMIT
I LIMIT
X
P LIMIT
P LIMIT
P LIMIT
X
IPEAK LIMIT
I PEAK LIMIT
IPEAKLIMIT
X
ALPHA IS RESTRICTED
ALPHA RESTRICTED
ALPHA
X
TS IS RESTRICTED
SWITCH ON TIME
TS
X
RESTRICTED
MAXIMUM CONTROLLER
MAXIMUM OUTPUT
MAXCONTROL
X
OUTPUT IS REACHED
REACHED
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
DESCRIPTION OF
THYRO-TOOL AX
MESSAGE
ACKNOWLEDGE VIA
MONITORING
MESSAGE
ON DISPLAY
LCD DISPLAY
U
MAINS
MIN
U MAIN < MINIMUM
UN MIN
X
U
MAINS
MAX
U MAIN > MAXIMUM
UN MAX
X
U
LOAD
MIN
U < MINIMUM
UL MIN
X
U
LOAD
MAX
U > MAXIMUM
UL MAX
X
I
LOAD
MIN
I < MINIMUM
IL MIN
X
I
LOAD
MAX
I > MAXIMUM
IL MAX
X
P
LOAD
MIN
P < MINIMUM
PL MIN
X
P
LOAD
MAX
P > MAXIMUM
PL MAX
X
R
LOAD
MIN
R < MINIMUM
RL MIN
X
R
LOAD
MAX
R > MAXIMUM
RL MAX
X
I
PEAK
MAX
I PEAK > MAXIMUM
I_PEAK MAX
X
* = cannot be deactivated
** = default setting of fault signaling relay K1: closed circuit principle
7.4 EASYSTART
In the case of the initial start of the device the managed parameteriza-
tion EasyStart is called up with the help of which the fundamental pa-
rameterization is configured. The following screens are depicted in the
displayed sequences. The ESC button calls up the previous page and as
such allows alterations to be made to settings already inputted.
During the configuration with EasyStart the pulse inhibition is active
and prevents power being emitted at the load side.
Start screen:
The parameterization of the fundamental values starts
with the button
Yes
. With
No
EasyStart is aborted, in
order, for example, to transfer an already saved parameter
file to the device using the Thyro-Tool AX.
Load factory settings:
The button Yes sets the Thyro-AX back to its default
settings. When pressing the button No, the Thyro-AX
continues EasyStart feature on basis of its current settings.
If EasyStart has been started once, it will request first the
default settings before EasyStart start screen appears.
Load type:
Here, adjustment to a purely ohmic load or an inductive
load, as occurs in transformers, is possible. As such in
case of a purely ohmic load the power controller can clock
more quickly with the
R-Load
setting and provides a larger
dynamic on the output side. Configuring a transformer
load with
RL-Load
causes an angle of the first half wave
(Alpha 1
st
) each time it switches through and an optimi-
zation of the necessary time intervals for the controlled
magnetization of the transformer coils.