V-line 899x.xxx
USER’S MANUAL
Enclosure no. 10
Conditions of wiring and operation of UPS for feeding a control system
and electronic part of V–line dispensers
1.
All the cooperating electronic circuits of the control system and dispensers must be
connected to the UPS and for this point of view they are considered as a closed
electronic unit.
2.
The control system and electronic instruments of dispensers connected to it as
a closed electronic unit must be connected only to one source of UPS.
3.
The feeding of perhaps even a part of the system from another source is not
permitted.
4.
A parallel cooperation of more UPS on one system is not permitted.
5.
"Live" conductors of control system supply circuits and dispenser electronic
equipment must be galvanic-separated from the mains and even from protective
conductors – a system of "swimming zero" is created.
6.
To comply with the requirement under item 5, the proper UPS must have galvanic-
separated input and output circuits.
7.
For feeding of electronic system of the filling station, the UPS of ON LINE type must
be used exclusively.
8.
For the correct function of UPS, the size of permanently installed load representing
max. 60 % of nominal UPS output, must be provided.
9.
To the stabilized voltage circuits, no other consumers that are not a part of
prescribed technology, can be connected.
10.
Therefore the sockets of stabilized voltage must be marked by the description e.g.
"Control system feeding".
11.
The protection of input circuits of UPS must be dimensioned so that UPS feed outage
and total battery discharge did not occur under standard equipment function.
Operating conditions of the V-line 899x.xxx/P fuel dispensers
(pressure design)
The pressure system of the distribution should be designed with a submerged pump built-in
directly into the storage tank under the substance level. The tank should be equipped with a
detector of the lowest substance level switching the el. circuit of the pump motor being the
min. level attained.
The location of the pump under the lowest fluid level in the storage tank and the min. level
control switch shall prevent the access of air or gas into the pump.
P12 = 0 parameter shall be preselected in the electronic counter for the pressure system of
submerged pumps operation in the storage tank in case of V-line 899x.xxx/P dispensers
operation. At first the electronic counter starts up the submerged pump in this mode of
operation (the fluid in entire hydraulic system is under pressure) then the counter tests the
displays and closes the el. magnetic valve - and the dispensing is started.
Содержание MINOR V-line 899 Series
Страница 2: ......
Страница 25: ...USER S MANUAL V line 899x xxx 21 Pic 6 Pic 7 ...
Страница 28: ...V line 899x xxx USER S MANUAL 24 Pic 15 Pic 16 ...
Страница 29: ...USER S MANUAL V line 899x xxx 25 Pic 10 Scheme of inputs and outlets of the unit VAPORIX Control ...
Страница 64: ......
Страница 69: ...USER S MANUAL V line 899x xxx Enclosure no 5 View of dispensers V line 899x 4x2 series ...
Страница 80: ...V line 899x xxx USER S MANUAL Enclosure no 16 V line dimensions of V line 899x 6x4 S P dispensers ...