to the price totalizer displays of the next dispensing nozzles by repeated depressing the "–" key or by
lifting the relevant nozzle).
6.
Terminate the scanning of electronic totalizers by depressing the "0" key and in case the thermal
and electronic calibration are activated, transition in the display mode of their setting occurs.
7.
The setting of thermal calibration for relevant nozzle is activated by the ATC text. The setting of
electronic calibration of the relevant nozzle counter is activated by the EC text.
8.
Terminate the scanning by depressing the "0" key and return to the standard mode.
8.4.4.
Check of vapour recovery system function
This function enables to carry out the independent check-up of vapour recovery from the tank without
fuel dispensing.
The check-up it is possible to activate by the help of KL-MANINF keyboard.
The necessary conditions for transition into the check of vapour recovery from the tank:
-
from last switch of the counter the dispensing nozzle wasn´t lifted
-
the transactions must be confirmed (unblocking by the help of RLS entry, if the parameter No. 4
value is 1
Notice:
KL-MANINF manager keyboards from the serial number 2110104000001 enable the activation of vapour
recovery check.
1.
Switch the power supply of the fuel dispenser off and wait for min. 30 s.
2.
Switch the power supply of the fuel dispenser on.
3.
With key „R“ on KL-MANINF keyboard choose the function of vapour recovery check The
text Vapour Check appears on the display.
4.
By dispensing nozzle lifting the vapour recovery system is activated. On the line of unit
price the value of the vapour recovery flow rate 20 l/min displays.
Notice: The dispensing nozzle is equipped with automatic valve which closes the vapour
recovery system, if the dispensing nozzle is hanged. Therefore it is necessary to knock
the nozzle down for releasing of the valve. During the all check it is necessary to keep
the nozzle in the down direction for not closing the valve not to stop vapour recovery.
5.
Put testing device (it is not a part of the dispenser delivery – can be ordered from the
producer – ELAFLEX Co.) on the nozzle up to the suction channel for vapour recovery or
if the testing device is not available, a plastic bag filled with air to cover the suction
channel, tight it well and by reducing of its volume check the function of vapour
recovery.
6.
The check of vapour recovery finish by hanging of all the dispensing nozzles and by
pressing of the key „R“. Than the counter will be returned to the mode of fuel
dispensing.
9.
MAINTENANCE OF A DISPENSER AND ITS INDIVIDUAL OPERATING
UNITS
The user of the dispenser is obliged to operate the device safely, reliably and in economic way. First of
all he is obliged to:
–
appoint a worker responsible for the operation and technical conditions of the dispenser and its
individual components
–
ensure inspection, testing, repairs and maintenance by qualified methods
–
carry out records and file documents - see point 3.2
ATTENTION!
All repairs of functional units may only be carried out by a service company and its
authorized personnel!
Содержание MINOR V-line 899 Series
Страница 2: ......
Страница 25: ...USER S MANUAL V line 899x xxx 21 Pic 6 Pic 7 ...
Страница 28: ...V line 899x xxx USER S MANUAL 24 Pic 15 Pic 16 ...
Страница 29: ...USER S MANUAL V line 899x xxx 25 Pic 10 Scheme of inputs and outlets of the unit VAPORIX Control ...
Страница 64: ......
Страница 69: ...USER S MANUAL V line 899x xxx Enclosure no 5 View of dispensers V line 899x 4x2 series ...
Страница 80: ...V line 899x xxx USER S MANUAL Enclosure no 16 V line dimensions of V line 899x 6x4 S P dispensers ...