manualshive.com logo in svg
background image

Installation & Operation Manual

 - Model VTS 

Contents of this Manual are Subject to Change Without Notification

 

Page 6 

2.1

 

Operating Range 

The operating range of each AccuStation is provided below along with a characteristic curve 
showing the relationship between the minimum operating pressure and maximum airflow 
volume as tested in accordance with ANSI/ASHRAE STD 130. 

 

 

 

 

 

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

25

50

75

100

125

150

175

200

225

250

275

300

325

St

at

ion D

P

 ("

wc)

Max Airflow (CFM)

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

100 150 200 250 300 350 400 450 500 550 600 650 700 750 800

St

at

ion D

P

 ("

wc)

Max Airflow (CFM)

0.00

0.05

0.10

0.15

0.20

0.25

0.30

0.35

0.40

0.45

100

200

300

400

500

600

700

800

900

1000 1100 1200 1300

St

at

ion D

P

 ("

wc)

Max Airflow (CFM)

6” Accu

Station 

Operating Range: 0-315 CFM 

Min. Measurement: 30 CFM 

8

” Accu

Station 

Operating Range: 0-800 CFM 

Min. Measurement: 80 CFM 

10

” Accu

Station 

Operating Range: 0-1300 CFM 

Min. Measurement: 120 CFM 

Содержание VTS

Страница 1: ...odel VTS Contents of this Manual are Subject to Change Without Notification Airflow Measurement Station Manufactured by Accutrol Representative VTS MANUAL REV A AccuStation 21 Commerce Drive Danbury C...

Страница 2: ...st defects or damages arising from improper installation where installation is by persons other than Manufacturer against defects in products or components not manufactured by Manufacturer or against...

Страница 3: ...TABLE OF CONTENTS LIMITED WARRANTY ii TABLE OF CONTENTS iii SECTION 1 INTRODUCTION 4 SECTION 2 SPECIFICATIONS 5 SECTION 3 PHYSICAL DIMENSIONS WEIGHTS 9 SECTION 4 INSTALLATION 10 SECTION 5 WIRING 13 S...

Страница 4: ...l pulses generated by each vortex shedding sensor are used to calculate the total airflow volume flowing through the AccuStation The transmitter provides a software selectable analog output signal tha...

Страница 5: ...s USB Configuration Port and Factory Cable Terminal Plugs 3 position vertical pluggable screw on top wire size 12 30 AWG EMC Safety EN 61326 1 2013 2014 35 EU LVD 2014 30 EU EMC EN 61010 1 2010 FCC Pa...

Страница 6: ...0 15 0 20 0 25 0 30 0 35 0 40 0 45 25 50 75 100 125 150 175 200 225 250 275 300 325 Station DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 100 150 200 250 300 350 400 450 500...

Страница 7: ...00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 300 600 900 1200 1500 1800 2100 2400 2700 Station DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 400 800 1200 1600 2000 2400 2...

Страница 8: ...05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 800 1600 2400 3200 4000 4800 5600 6400 Station DP wc Max Airflow CFM 0 00 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 1000 2000 3000 4000 5000 6000 7000 80...

Страница 9: ...imensions are to the outside and have a tolerance of 062 1 6mm Model Size Dimensions Weight D L H Stainless Steel Aluminum in mm in mm in mm Lbs kg Lbs kg 06 5 88 149 22 559 10 254 11 5 0 7 3 2 08 7 8...

Страница 10: ...be sure to select a location that will provide a minimum clearance of 14 356mm unobstructed access to the transmitter and station access cover 3 Provide an opening in the duct section sized appropria...

Страница 11: ...ARGE INLET 4 Secure station to duct using tek screws 6 Secure both ends of station to the duct using draw band clamps 2 Slip the station inlet into the fan side of the duct far enough to allow the sta...

Страница 12: ...sed Also verify both ends of the duct where the station is to be attached are true and square before attempting to install station If the duct ends are not square and true do not attempt to install st...

Страница 13: ...gure below is shown with the optional BACnet module installed and the remote monitor connected 24 vAC 24 vDC or Analog Input BMS Controller Signal Receiving Device Common Power Source BACnet MSTP Bus...

Страница 14: ...om the factory by performing the following steps Note This process will require an automatic email to be generated from your computer therefore you will need to have internet access to generate the ke...

Страница 15: ...transmitter through the computer connected to the USB Configuration Port This is a temporary position only Note The Power Source Switch must be returned to the Operational Position after completing th...

Страница 16: ...lect Locate Accutrol Devices then select the com port associated with the VTS that your computer is connected to 6 5 1 Insight Dashboard The Insight Dashboard is the primary screen for accessing the t...

Страница 17: ...log Output or it can be configured with a full scale range that is independent of the Analog Output To change the full scale range click on the gauge face 6 5 5 Analog Output Configuration The VTS s A...

Страница 18: ...Source Manual Output 6 5 6 Sensor Frequency Signals The AccuStation measures airflow using vortex shedders that are incorporated in the compression zone of each chamber inside the station Each vortex...

Страница 19: ...rom the factory The current configuration settings will be replaced Save To Transmitter Flash Memory This will save the contents of the transmitter RAM memory to the transmitter nonvolatile FLASH memo...

Страница 20: ...uStation or advisable and is only provided as a tool for the Airflow Balancer to correlate the VTS airflow measurement to a field airflow measurement The graph below shows the effect the Equal Cal Adj...

Страница 21: ...output full scale range BACnet Configuration Opens a window required for configuring the BACnet VIEW System Info Provides the status of Transmitter connections Transmitter Identification Provides the...

Страница 22: ...utrol VTS Transmitter product family supports a collection of BACnet visible objects which are defined in the following table Point Object Description Present Value Type Units DE Device Instance Write...

Страница 23: ...es which are not retained when the power to the transmitter is lost Values stored in Flash memory are copied to RAM memory during the power up sequence of the transmitter Writing a value of one 1 to t...

Страница 24: ...lt enough to allow the access door to slide forward CAUTION If the bolt is removed from the captive nut the access cover can spring open possibly causing injury 8 1 2 Using two hands squeeze the acces...

Страница 25: ...ver is secured to the station using 4 2 blunt head Phillips head screws To inspect the sensors remove the access cover by removing the screws using a 2 Phillips head screw driver Put the screws aside...

Отзывы: