Installation & Operation Manual
- Model VTS
Contents of this Manual are Subject to Change Without Notification
Page 17
6.5.2 Airflow Volume Gauge
The Airflow Volume Gauge provides the real-time measurement of the volumetric air flowing
through the AccuStation. The range of this gauge is determined by the size of the station and it
cannot be reset in the field.
6.5.3 Station Airflow Gauge
The Station Airflow Volume Gauge provides the real-time measurement of the volumetric air
flowing through the AccuStation. The range of this gauge can be configured to match the full-
scale range of the Analog Output or it can be configured with a full-scale range that is
independent of the Analog Output. To change the full-scale range, click on the gauge face.
6.5.5 Analog Output Configuration
The VTS
’s
Analog Output is primarily used to provide an analog signal representing the Airflow
Volume flowing through the station. The signal type and full-scale range of the Analog Output
are user-defined values that are configured by clicking on the boxes adjacent to each heading.
The Analog Output can be configured to Manual Override if desired.
Select Signal Source
; Station Airflow or Manual Output
Select Signal Type
; 0-20mA, 4-20mA, 0-5V, 1-5V, 0-10V, 2-10V
Enter
the Analog Output
Full Scale Range
Displays the real time value based on the Full Scale units
Displays the real time analog signal value