Installation & Operation Manual
- Model VTS
Contents of this Manual are Subject to Change Without Notification
Page 5
SECTION 2 - SPECIFICATIONS
PERFORMANCE
Accuracy +/- 5% of reading or 5 CFM, whichever is greater
Min Operating Pressure Reference Section 2.1
Airflow Range Reference Section 2.1
ENVIRONMENTAL
Temperature Airstream: -20 to 165 deg. F
Ambient: -20 to 125 deg. F
Storage: -40 to 165 deg. F
Humidity 0 to 90% non-condensing
TRANSMITTER ELECTRICAL
Power Supply 24 VAC +/- 20% 50/60 Hz, 4 VA max (8.5 VA max with remote monitor)
24 VDC +/- 10% 1.5 W max (3.5 W max with remote monitor)
Output Signal Software Configurable; 0-20mA, 4-20mA, 0-10V, 2-10V, 0-5V, or 1-5V
12-bit Resolution capable of driving 1K-ohm load
Configuration Port USB 2.0, Isolated, C Type Connector
Power Source Switch Operational Position: Draws power from 24V input terminal block
Nonoperational Position: Draws power from 5V USB port (Use for configuration only)
BACnet MS/TP
(Optional)
EIA 485 2-wire BACnet MS/TP, Galvanically Isolated
Data Rates 9600, 19200, 38400, 57600, 76800 and 115200
1/8 Unit Load Receiver Input Impedance
Network bias and EOL Termination not provided within the Transmitter
Remote Monitor
Sold
Separately
LCD, 2 lines x 8 characters with white LED backlight
Includes USB Configuration Port and Factory Cable
Terminal Plugs 3-position, vertical pluggable, screw on top, wire size 12-30 AWG
EMC
Safety
EN 61326-1:2013, 2014/35/EU (LVD), 2014/30/EU (EMC)
EN 61010-1:2010
FCC Part 15
This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be required to correct the
interference at the user’s own expe
nse. This Class A digital apparatus meets all requirements
of the Canadian Interference-Causing Equipment Regulations.
Model Code Material
Designator
(2) 304SS
(3) 316SS
(4) Aluminum
Housing
304L SS
316L SS
Alum. 5052-H32
Compression Section
304L SS
316L SS
Alum. 5052-H32
Static Regain Section
304L SS
316L SS
Alum. 5052-H32
End Plate
304L SS
316L SS
Glv. Steel
Vortex Sensors
Polycarbonate
UL94-VO
Polycarbonate
UL94-VO
Polycarbonate
UL94-VO
Sensor Tubing
Polyurethane,
Ether-based
Polyurethane,
Ether-based
Polyurethane,
Ether-based
MATERIALS OF CONSTRUCTION (In Airstream)