60
Acuvim-L
The 14
th
screen: DO2 inequality sign setting.
0: < (less than); 1: > (greater than)
Press “V/A” to accept change and proceed to the
next page.
The 15
th
screen: DO2 alarm limit setting.
Set the alarming limit value for the tracking
parameter.
Refer to Chapter 3.8 << Measurement Methods
and Parameter Definitations>> for alarm limit
value setting details.
As shown in Fig.3-70, the DO2 limit is set to 4500.
This is the last screen of DO parameter setting.
The 16
th
screen: backlight blinking setting. If the
alarm backlight blinking is enabled, the screen
displays “1”.
As show in Fig.3-71, the backlight
blinkingis enabled. Under this circumstance, when
an alarm is triggered, the backlight will be blinking
at the same time. Press “P” or “E” to choose between
“0” and “1”.
Fig.3-69 DO2 inequality sign setting
Fig.3-70 DO2 alarm limit setting
ALUM0363
ALUM0362
Fig.3-71 alarm back light blink setting
ALUM0364