49
Acuvim-L
Note: The page is only shown in Acuvim-EL and KL. “non1” represents non-parity,
single stop bit; “non2” represents non-parity, double stop bit; “odd” represents
odd-parity, single stop-bit; “EVEN” represents even parity, single stop bit. By
default it is set as “EVEN”.
The 4
th
screen: Voltage input wiring setting.
Voltage input could be one of five setting:3LN,
3LL, 2LL, 1LL, 1LN.
As shown in Fig.3-40: voltage input mode is set to
3LN.
Press “P” or “E” to select a wiring mode, press “V/A” to
accept the change and proceed to the next page.
The 5
th
screen: Current input wiring setting.
Current wiring mode can be one of the three
settings: 3CT, 2CT, 1CT. As shown in Fig.3-41,
current input mode is set to 3CT
Press “P” or “E” to select a wiring mode, press “V/
A” to accept the change and proceed to the next
page.
The 6
th
screen: PT primary side ratio setting.
PT1 ratio can be set from 50.0 to 1,000,000.0 (unit
in V)
As shown in Fig.3-42, PT1=380.0V.
To change PT1 value, press “H” to move the
cursor, press “P” to increase value by 1, press “E”
to decrease value by 1. Press “V/A” to store the
current value and proceed to the next screen.
Fig.3-40 Voltage input wiring setting
Fig.3-41 Current input wiring setting
ALUM0338
ALUM0337
ALUM0339
Fig.3-42 PT primary side ratio setting