171
Acuvim-L
3D2H DI counter clear
0x0A: clear
Other: NONE
R/W
The address area contains pulse counter number. The pulse counter number could be
reserved with power-down, it also could be clear through PC software.
DI counter parameter:03H Read;10H Write
0x3A0H~0x3A1H
DI1 counter number
0-4294967295
Dword
0x3A2H~0x3A3H
DI2 counter number
0-4294967295
Dword
0x3A4H~0x3A5H
DI3 counter number
0-4294967295
Dword
0x3A6H~0x3A7H
DI4 counter number
0-4294967295
Dword
It contains 20 SOE events during 0x300 and 0x363 address area, it indicates 1st SOE
event address area from 0x300H to 0x304, the format as: year-month, day-hour,
minute-second, millisecond and DI state. The other’s format is same as first event.
Table 4-44 SOE event parameter address area
SOE event record area: 03H Read
0x300H
Year of 1st SOE Event(High Byte)
00-99
word
Month of 1st SOE Event(Low Byte)
1-12
0x301H
Day of 1st SOE Event(High Byte)
1-31
word
Hour of 1st SOE Event(Low Byte)
0-23
0x302H
Minute of 1st SOE Event(High Byte)
0-59
word
second of 1st SOE Event(Low Byte)
0-59
0x303H
Millisecond of 1st SOE Event
0-999
word
0x304H
1
st
SOE event state
0-15
word
0x305H~0x309H
2
nd
SOE event
same
word
0x30aH~0x30eH
3
th
SOE event
same
word