143
Acuvim-L
Parameter setting
Function code: 03 read; 16 preset
Address
Parameter
Type of
acccess
Data type
Data
type
0100H
Access code
R/W
0~9999
word
0101H
Communication
address
R/W
1~247
word
0102H
Baud rate
R/W
1200~57600
word
0103H
Voltage wiring type
R/W
0: 3Ln; 1: 3LL; 2: 2LL; 3: 1Ln; 4: 1LL
word
0104H
Current wiring
type
R/W
0: 3CT; 1: 2CT; 2: 1CT
word
0105H
PT1(high 16 bit)
R/W
50.0~1000000.0
word
0106H
PT1(low 16 bit)
R/W
word
0107H
PT2
R/W
50.0~400.0
word
0108H
CT1
R/W
1~50000
word
0109H
CT2
R/W
1 , 5 or 333
word
010AH
Definition of ractive
power
R/W
0: sinusoidal
1: nonsinusoidal
word
010BH
Backlignt time
R/W
0~120(min)
word
010CH
Time of demand
slide window
R/W
1~30
word
010DH
Clear max
R/W
0AH:clear
word
010EH
Clear energy
enable
R/W
0:disable;1:enable
word
010FH
Clear energy
R/W
0:disable; 0AH:enable
word
0110H
Clear runhour
R/W
0AH:clear,other:do not clear
word
0111H
Clear load runhour
R/W
0AH:clear,other:do not clear
word
0112H
Parity check choice
R/W
0: EVEN; 1: odd; 2: NON2; 3:NON1
word
0113H
VAR/PF choice
R/W
0:IEC;1:IEEE
word
Table4-35 Data address of setting parameter
Shop for Power Metering products online at:
1.877.766.5412
www.
PowerMeterStore
.com