136
Query
Table 5-19 Read 2 Relays Status Query Message
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi
Length lo
Unit
identifier
00H
00H
00H
00H
00H
06H
01H
Fun
Data start reg hi
Data start reg lo
Data #of regs hi
Data #of regs lo
01H
00H
00H
00H
02H
Response
The AcuRev 2000 series meter response includes MBAP Header, function code, quantity of
data byte and the data. For example response to read the status of Relay 1 and Relay 2 is
shown as Table 5-6. The status of Relay 1 and Relay 2 is responding to the last 2 bit of the
data.
Table 5-20 Read 2 Relays Status Response Message
Relay 1: bit0
Relay 2: bit1
Transaction
identifier hi
Transaction
identifier lo
Protocol
identifier hi
Protocol
identifier lo
Length hi Length lo
Unit
identifier
00H
00H
00H
00H
00H
04H
01H
Fun
Byte count
Data
01H
01H
02H
The content of the data is,
7
6
5
4
3
2
1
0
0
0
0
0
0
0
1
0
MSB LSB
(Relay 1 = OFF , Relay 2=ON)
Содержание AcuRev 2000
Страница 1: ...User s Manual AcuRev 2000 Smart Metering System...
Страница 2: ......
Страница 8: ...VI...
Страница 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Страница 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 40: ...32...
Страница 93: ...85 Figure 4 7 Demand...
Страница 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Страница 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Страница 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Страница 152: ...144 Figure 5 18...
Страница 158: ...150 Figure 5 23...
Страница 165: ...157 Request binding 1 phaseVoltageA 0 null null Response binding 1 phaseVoltageA 0 integer 0 Figure 5 29...