4. Control Relay Output (Function Code 05)
Query
This query frame forces the relay status to ON or OFF. Data FF00H sets the relay as ON, and
data 0000H sets the relay as OFF. The relay will not be influenced by any other data input
The following is to query slave device 17 to set relay status as ON.
Addr
Fun
DO addr
hi
DO addr
Lo
Value
Hi
Value
lo
CRC16
hi
CRC16
lo
11H
05H
00H
00H
FFH
00H
8EH
AAH
Table 5-10 Control relay status query frame
Response
The correct response to this request is to send back the received data after the relay status
is changed.
Addr
Fun
Do addr
Hi
Do addr
Lo
Value
Hi
Value
Lo
CRC16
Hi
CRC16
Lo
11H
05H
00H
00H
FFH
00H
8EH
AAH
Table 5-11 Control relay status response frame
Содержание AcuRev 2000
Страница 1: ...User s Manual AcuRev 2000 Smart Metering System...
Страница 2: ......
Страница 8: ...VI...
Страница 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Страница 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 40: ...32...
Страница 93: ...85 Figure 4 7 Demand...
Страница 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Страница 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Страница 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Страница 152: ...144 Figure 5 18...
Страница 158: ...150 Figure 5 23...
Страница 165: ...157 Request binding 1 phaseVoltageA 0 null null Response binding 1 phaseVoltageA 0 integer 0 Figure 5 29...