Aux. Power Supply
AcuRev 2000 power supply is 100-415Vac, 50/60Hz or 100-300Vdc, which are universally
supported.If any other power supply is required, please contact the manufacturer.The
power consumption of the power meter is low during normal operation, therefore, the
power supply can be either via a standalone power supply or via the measured circuit. A
regulator is recommendended where the voltage is not stablized.The power supply
terminal number is L/N/G.
Figure 2-23 Power Supply wiring
Power Supply wiring is AWG22~16 or 0.6~1.5mm
2
.
A fuse or small size circuit breaker is mandotary for AcuRev 2000 Power Supply. The fuse
recommendation is 1A/250Vac, time delay.If a circuit breaker is utilized, it must be CE
certified and comply with IEC 947 standard.
An isolated transformer or EMC flter should be used in the auxiliary power supply loop if
there is a power quality problem in the power supply.
Figure 2-24 Power Supply wiring
1A FUSE
Power Supply
AcuRev2000
L
N
L
N
L
N
13
14
Содержание AcuRev 2000
Страница 1: ...User s Manual AcuRev 2000 Smart Metering System...
Страница 2: ......
Страница 8: ...VI...
Страница 9: ...1 1 1 Meter Overview 1 2 Areas of Application 1 3 AcuRev 2000 features Chapter 1 Introduction...
Страница 15: ...7 Chapter 2 Installation 2 1 Appearance and Dimensions 2 2 Installation Methods 2 3 Wiring...
Страница 40: ...32...
Страница 93: ...85 Figure 4 7 Demand...
Страница 101: ...93 4 6 Over Under Limit Alarming Figure 4 13 Alarming in software...
Страница 104: ...96 Figure 4 15 System Event Log 4 7 System Event Log...
Страница 120: ...112 4 10 Device Information Figure 4 18 Device Information...
Страница 152: ...144 Figure 5 18...
Страница 158: ...150 Figure 5 23...
Страница 165: ...157 Request binding 1 phaseVoltageA 0 null null Response binding 1 phaseVoltageA 0 integer 0 Figure 5 29...