70
AcuDC 210/220 Series
4. Input
Current
Current
0~10A(Direct Input), 0~9999A(Extra current shunt or HCT, with
programmable range)
Shunt
50~100mV(Programmable)
Hall Current Thruster (HCT)
0~5V, 0~4V, 0~20mA, 4~20mA
Power Consumption
2W(Max)
Accuracy
0.2%
Voltage
Input Voltage
0~600V
Input Impedence
2MΩ
Load
< 0.2W
Digital Input (DI)
Isolate Voltage
2500Vac rms
Input Type
Wet contact (Contact with power supply)
Input Resistance
2K ohm (typical)
Input Voltage Range
16~30Vdc
Max Input Current
20mA