59
AcuDC 210/220 Series
3. Read Data (Function Code 03)
Query
This function allows the master to obtain the measurement results from the meter.
Table 4.8 is an example to read the measured data from slave device number 1, the
data address for voltage V is 0200H.
Addr
Fun
Data start
addr HI
Data start
Addr LO
Data # of
regs HI
Data # of
regs LO
CRC16
HI
CRC16
LO
01H
03H
02H
00H
00H
01H
85H
B2H
Response
The meter response includes the meter address, function code, quantity of data
byte, data, and error checking. An example response to read V=0001H (0.01V) is
shown in Table 4.9.
Addr
Fun
Byte
count
Data
HI
Data
LO
CRC16
HI
CRC16
LO
01H
03H
02H
00H
01H
79H
84H
Table 4.8 Read V Query Message
Table 4.9 Read V Message