27
AcuDC 210/220 Series
value. The lower limit must be equal to or greater than 0. Appropriate upper and
lower limit settings help to increase tracking accuracy and efficiency.
3. The relationship among AO output(out), upper limit(U) and lower limit(L) and
measuring value(M) is as follows:
1): Voltage output option for AO: out=[(M-L)/(U-L)]*5V
2): Current output option for AO: out=4+[(M-L)/(U-L)]*16mA
Two examples will be used to demostrate the above two relationships.
AO tracking object and its setting is as follows:
Setting number
Tracking object
0
Voltage
1
Current
2
Power
Table 2.3 Tracking object and its Setting number