47
AcuDC 210/220 Series
010FH
0100H
Alarming value
current: 0~9999.0
voltage: 0~600.0
power: 0~ 6000.0
010DH
Alarming delay time
0~255 s
010EH
RO alarm channel
0~RO1; 1~RO2; 2~RO1,RO2
Here is an example to show how this works
If we want to trigger an alarm at RO1 when the current is over 10.005A with a time
delay of 15 seconds, we should set the alarm parameters as follows:
1) Set RO1 output mode to 2 (This means RO1 works under alarming mode).
2) Set alarming object to 2 (current). The alarming limit value should be set as
10.005.
3) Set alarming delay time as 15 seconds.
4) Set sign of inequality to 1.
5) Set RO alarm output channel as 0.
After setting up the alarm parameters, when the alarm condition is met (current
goes above 10.005A for 15 seconds), RO1 will be activated (contact closed) and the