24
AcuDC 210/220 Series
The external power supply voltage range for DI is from 16Vdc to 30Vdc. In order to
compensate for interference, voltage of the external power supply may be higher
when the DI's load is located at a distance; however, the maximum currert for the
circuit must not be over 20mA. Wires with cross-section of 0.6~1.5mm
2
(AWG
16~22) should be used for DI.
Relay Output
Two relay outputs (RO), R11,R12 (terminal 16, 17) and R21, R22 (terminal 18,19), can
be added to the meter as options.
ROs can be used as remote control electric switches in power systems. Relay
type is mechanical Form A contact with 3A/250V or 3A/30Vdc. A mediate relay is
recommended in the output circuit as in Fig 2.18.