AcuDC 210/220 Series
The third screen: Shunt / Hall Effect Sensor
current input full range setting. The value
input is the full range current value for the
Shunt or Hall Effect Sensor. AcuDC 210/220
series support 1~9999A shunt. The value
range in this screen is 1~9999.
The fourth screen: Shunt / Hall Effect Sensor
output voltage setting. The value input is the
full range output voltage value for the Shunt
or Hall Effect Sensor. For instance, 100mV
shunt, enter 100; 5V Hall Effect Sensor, enter 5;
20mA Hall Effect Sensor, enter 20.
AcuDC 210/220 series support 50~100mV arbitrary voltage shunt. If it exceeds
this range, the value will be reset to default 100. Our recommendation for shunt is
100mV shunt, it is better for accuracy.
In this shunt scenario, the range is 50~100; for volage Hall Effect Sensor, the range is
1~100; for current Hall Effect Sensor, the range is 4-100. 4~XmA and 0~XmA types
are not exchangable.
A
Fig 3.10 Shunt current input full range setting
Fig 3.11 Shunt/Hall Effect Sensor output setting