Outdoor Unit Disassembly
11
3.6
Four-way valve (for heat pump models)
WARNING:
Evacuate the system and confirm that there is no refrigerant left in the system before removing the
four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be
implemented by professionals.)
Note: Remove the panel plate, connection of four-way valve on PCB (refer to 3.1 Panel plate and 3.2 Electrical
parts) before disassembling sound blanket.
Procedure
Illustration
1) Heat up the brazed parts and then detach
the the four-way valve and the pipe (see
CJ_ODU_VALVE_001).
2) Remove the four-way valve assembly with
pliers.
CJ_ODU_VALVE_001
Note: This section is for reference only. Actual unit appearance may vary.
Содержание COLONNA CLN130R
Страница 2: ...R32 DC Inverter Floor standing Type Air conditioner unit SERVICE MANUAL 09 2022 MTE01004I0120 00...
Страница 3: ......
Страница 6: ......
Страница 7: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 13: ...Contents 1 Model Reference 2 2 Pipe Length and Drop Height 3 3 Electrical Wiring Diagrams 4 Specifications...
Страница 19: ...Specifications 7...
Страница 20: ...Outdoor unit printed circuit board diagram 17122000041841 Specifications 8...
Страница 22: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4 Specifications 10...
Страница 41: ...Indoor Unit Disassembly 2 1 Dimension...
Страница 57: ...Outdoor Unit Disassembly 3 2 Dimension UECS130R...
Страница 100: ...For some models 33...