2. Pipe Length and Drop Height
The length and elevation of connection pipe are shown in the table below. if the pipe length exceeds max pipe length,
additional refrigerant should be charged to ensure nominal cooling/heating capacity.
Capacity(Btu/h)
Standard Length
Max Pipe Length
Max Elevation
Additional Refrigerant
48k
5m (16.4ft)
65m(213.25ft)
30m(98.4ft)
24g/m (0.26oz/ft)
If oil flows back into the outdoor unit’s compressor, this might cause liquid compression or deterioration of oil return. Oil
traps in the rising gas pipe can prevent this.
-An oil trap should be installed every 6m(20ft) of vertical suction line riser (
<
36000Btu/h unit).
-An oil trap should be installed every 10m(32.8ft) of vertical suction line riser (≥36000Btu/h unit).
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (
<
36000Btu/h unit)
10m/32.8ft (≥36000Btu/h unit)
6m/20ft (
<
36000Btu/h unit)
Indoor unit/
Outdoor unit
Indoor unit/
Outdoor unit
Specifications 3
Содержание COLONNA CLN130R
Страница 2: ...R32 DC Inverter Floor standing Type Air conditioner unit SERVICE MANUAL 09 2022 MTE01004I0120 00...
Страница 3: ......
Страница 6: ......
Страница 7: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 13: ...Contents 1 Model Reference 2 2 Pipe Length and Drop Height 3 3 Electrical Wiring Diagrams 4 Specifications...
Страница 19: ...Specifications 7...
Страница 20: ...Outdoor unit printed circuit board diagram 17122000041841 Specifications 8...
Страница 22: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4 Specifications 10...
Страница 41: ...Indoor Unit Disassembly 2 1 Dimension...
Страница 57: ...Outdoor Unit Disassembly 3 2 Dimension UECS130R...
Страница 100: ...For some models 33...