Troubleshooting
Index:
1. Normal voltage of P and N
208-240V(1-phase,3-phase)
380-415V(3-phase)
In standby
around 310VDC
around 530VDC
In operation
With passive PFC module
With partial active PFC
module
With fully active PFC
module
/
>200VDC
>310VDC
>370VDC
>450VDC
2. Reactor Check
Measure the resistance and voltage (to ground) of the reactor. The normal resistance should be around 0.1 ohm. Otherwise,
the reactor must have malfunction.
40