Product Features
5
3.2 Abbreviation
Unit element abbreviations
Abbreviation
Element
T1
Indoor room temperature
T2
Coil temperature of evaporator
T3
Coil temperature of condenser
T4
Outdoor ambient temperature
TS
Set temperature
TP
Compressor discharge temperature
In this manual, such as CDIFTEMP, HDIFTEMP2, TCE1,
TCE2...etc., they are well-setting parameter of EEPROM.
3.3 Fan Mode
When fan mode is activated:
• The outdoor fan and compressor are stopped.
• Temperature control is disabled and no temperature
setting is displayed.
• The indoor fan speed can be set to high, low, or auto.
• The louver operations are identical to those in cooling
mode.
• Auto fan: In fan-only mode, AC operates the same as
auto fan in cooling mode with the temperature set at
24°C.
3.4 Cooling Mode
3.4.1 Compressor Control
Reach the configured temperature:
1) When the compressor runs continuously for less than
120 minutes.
• If the following conditions are satisfied, the
compressor ceases operation.
• While calculated frequency(fb) is less than minimum
limit frequency(FminC).
• While protective time is more than or equal to ten
minutes.
• While T1 is lower than or equal to (Tsc-CDIFTEMP-
0.5°C)
Note: CDIFTEMP is EEPROM setting parameter. It is 2°C
usually.
2) When the compressor runs continuously for more than
120 minutes.
• If the following conditions are satisfied, the
compressor ceases operation.
• When calculated frequency(fb) is less than minimum
limit frequency(FminC).
• When protective time is more than or equal to ten
minutes.
• When T1 is lower than or equal to (Tsc-CDIFTEMP).
Note: CDIFTEMP is EEPROM setting parameter. It is 2°C
usually.
3) If one of the following conditions is satisfied, not judge
protective time.
• Compressor running frequency is more than test
frequency.
• When compressor running frequency is equal to
test frequency, T4 is higher than 15°C or T4 sensor
fault
• Change setting temperature.
• Turbo function on/off
• Various frequency limit shutdown occurs.
3.4.2 Indoor
Fan Control
• In cooling mode, the indoor fan operates continuously.
The fan speed can be set to high, (medium),low, or
auto.
• Auto fan in cooling mode:
3.4.3 Outdoor
Fan Control
Case 1:
• The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
• For different outdoor units, the fan speeds are
different.
Case 2:
• The outdoor unit will be run at different fan speed
according to T4.
• For different outdoor units, the fan speeds are
different.
Содержание COLONNA CLN130R
Страница 2: ...R32 DC Inverter Floor standing Type Air conditioner unit SERVICE MANUAL 09 2022 MTE01004I0120 00...
Страница 3: ......
Страница 6: ......
Страница 7: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 13: ...Contents 1 Model Reference 2 2 Pipe Length and Drop Height 3 3 Electrical Wiring Diagrams 4 Specifications...
Страница 19: ...Specifications 7...
Страница 20: ...Outdoor unit printed circuit board diagram 17122000041841 Specifications 8...
Страница 22: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4 Specifications 10...
Страница 41: ...Indoor Unit Disassembly 2 1 Dimension...
Страница 57: ...Outdoor Unit Disassembly 3 2 Dimension UECS130R...
Страница 100: ...For some models 33...