30 Planning and Installation Guidelines
Planning and
Installation Guidelines
Technical Description
Wireless Proximity Switches / Issue: 09.2004
V 6
Setting of the Cell-ID range identification for the input module
During comissioning, each input module needs an individual Cell-ID range identification
between 1 and 60. This Cell-ID range identification guarantees that also in large installations
with more than 120 wireless proximity switches (i.e. also more than one input module) the
proximity switches communicate reliably with their assigned input module.
In the case of repeated use of a Cell-ID range identification (i.e. already more than 60 input
modules are installed) the distance, between proximity switches and the pair of antennas of
the not assigned input module with the same Cell-ID - range identification, should amount to
at least 50 m.
CELL ID
32
CELL ID
Change CELL ID?
Procedure
Description
Display content *)
Operator
options
SET-MAIN menue
SET
/\
or
\/
Change to another mode except RUN
Change to RUN mode
Change to system settings
/\
or
\/
ESC
OK
CELL ID
12
/\
or
\/
ESC
OK
Change to another systen setting in the SET-mode
Change to SET-MAIN menue
Change for editing of the Cell-ID range identification
OK, /\
or
\/
/\
or
\/
ESC
OK
Increase or decrease of the chosen number (blinks);
range from 01 … 60
Leave editing mode
Change to the next number ;
Confirmation of the Cell-ID after the last number
OK, /\
or
\/
ESC
OK
Leave edit mode
Confirmation of the Cell-ID and leave edit mode
OK
CELL ID
32
/\
or
\/
ESC
OK
Change to another systen setting in the SET-mode
Change to SET-MAIN menue
Change for editing of the Cell-ID
OK
*) All sensor information and cell-ID identifications are examples; XXX stands for blinking display