Planning and Installation Guidelines 29
Planning and
Installation Guidelines
Technical Description
Wireless Proximity Switches / Issue: 09.2004
V 6
3.8 SET Mode
System settings at the input module
By simultaneously pressing of
ESC
and
OK
from the RUN mode, the CFG mode is reached.
From there the SET mode is reached via \/. This mode offers the following options:
•
Setting the field bus address
•
Setting of the Cell ID (range identification)
•
Setting of the password
•
Resetting of the input module to factory settings
•
Choosing the reference configuration for start-up (local / via field bus)
•
Display of field bus parameters
•
Entry of the master password
Setting of the field bus address for the input module
The input module communicates over a FieldBusPlug and a fieldbus with a machine control.
The necessary field bus address is specified in the following dialogue.
The system menus permits addresses between 0 and 255. Which address ranges are actually
available for the integration into a field bus structure, depends on the installed field bus and the
already existing field bus participants.
FIELDBUS ADDR
102
FIELDBUS ADDR
Change FB Addr?
Procedure
Description
Display content *)
Operator
options
SET-MAIN menue
SET
/\
or
\/
Change to another mode except RUN
Change to RUN mode
Change to system settings
/\
or
\/
ESC
OK
FIELDBUS ADDR
002
/\
or
\/
ESC
OK
Change to another systen setting in the SET-mode
Change to SET-MAIN menue
Change for editing of field bus address
OK
/\
or
\/
ESC
OK
Increase or decrease of the chosen number (blinks);
range from 000 .. 255
Leave editing mode
Change to the next number ;
Confirmation of the field bus address after the last
number
OK, /\
or
\/
ESC
OK
Leave edit mode
Confirmation of the field bus address and leave edit
mode
OK
FIELDBUS ADDR
102
/\
or
\/
ESC
OK
Change to another systen setting in the SET-mode
Change to SET-MAIN menue
Change for editing of field bus address
OK
The address „000“ is preset, which is invalid with ProfiBus. The FieldBusPlug uses its previous
field bus address automatically in this case!
*) All sensor information and cell-ID identifications are examples; XXX stands for blinking display