22 Planning and Installation Guidelines
Planning and
Installation Guidelines
Technical Description
Wireless Proximity Switches / Issue: 09.2004
V 6
The input module provides connection between the wireless proximity switches and the machine
control via an ABB FieldBusPlug.
It makes the following information available for the machine control:
Status of each sensor
0: Sensor not damped
1: Sensor damped
Valid for each sensor
0: Sensor status invalid or sensor not configured
1: Sensor status valid
Configuration error
The actual configuration of the installation does not match the
configuration of the input module. Sensors are missing.
System error
Malfunction of a configured sensor
Run/Config
0: The input module is in Run mode
1: The input module is in Config mode
Error acknowledge
0
→
1: Reset of present error messages
WINK
0
→
1: Set WINK command for a selected sensor
1
→
0: Terminate WINK mode for a selected sensor
3.
Input module
3.1 Functions of the input module
The following function2ality is offered by the input module
•
choice between the modes:
o
RUN:
Operation
o
CFG:
Configuration of wireless proximity switches
o
DEL:
Delete the configuration of wireless proximity switches
o
SET:
Settings
•
Individual display of the information to configured wireless proximity switches in operation
•
Triggering of the WINK mode for a selected sensor for clear allocation during operation
•
Acknowledgement of error messages during operation
•
Adding further wireless proximity switches (configuration)
•
Deletion of configured wireless proximity switches
•
Setting of a password for prevention of unauthorized changes at the input module
•
Setting of an cell-ID address for the input module
•
Setting of a field bus address