1
X
X
4
18
UNISEC DY800 - E D. 4 - ACCORDING TO E- DISTRIBUZIONE SPECIFIC ATIONS
- INS TA LL ATI ON M A NUA L
giunzione visto dall'alto
Particolare della
4
3
2
4
5 3
2
Detail of junction
viewed from above
– move the second cubicle close to the first so that
their sides touch each other;
– fit the M4 screws into the holes marked X and fully
tighten the bolts into the adjacent cubicle;
– fit the fastening screw into the slot (1) and into the
adjacent cubicle, then fully tighten the bolt.
Repeat these operations for the successive cubicles
and after they have been joined together, fix the
cubicles to the floor and fully tighten the screws.
Make sure that the sides of the cubicles are right up
against each other and that there are no gaps at the
front towards the busbar compartment (5).
DY800/316 cubicles
– position the first cubicle on a level with the holes
in the floor;
– fit the fastening bolts into the floor and screw
them in but without fully tightening them;
– move the second cubicle close to the first so that
their sides touch each other;
– fit the M4 screws into the holes marked X and fully
tighten the bolts into the adjacent cubicle;
– fit the M10 screws into the holes marked Y and
fully tighten the bolts into the adjacent cubicle;
– Repeat these operations for the successive
cubicles and after they have been joined together,
fix the cubicles to the floor and fully tighten the
screws.
Make sure that the sides of the cubicles are right up
against each other and that there are no gaps at the
front towards the busbar compartment.
In the case of end panels, the screws
and nuts must still be fitted into the
indicated points to ensure the IP3X
protection class
8.6 Joining and fastening
the cubicles
Make sure that the floor is flat before joining the
cubicles.
The cubicles must be joined in the following way:
DY800/116 cubicles
– unscrew the screws (2) and eyebolts (3) from the
roofs of the cubicles
– position the first cubicle on a level with the holes
in the floor
– fit the fastening bolts into the floor and screw
them in but without fully tightening them;
—
8. Installation
X
Y
Y