4
UNISEC DY800 - E D. 4 - ACCORDING TO E- DISTRIBUZIONE SPECIFIC ATIONS
- INS TA LL ATI ON M A NUA L
—
3. Storage
—
2. Checking on receipt
The cubicles must be unloaded from the transport
with the utmost care, as described in chap. 5.
Upon receipt, immediately check the condition of
the pack, that the apparatus is undamaged and that
the data on the nameplate on the outside of the
packaging correspond to the information in the
order confirmation and shipping note.
If damage or discrepancies are discovered, or the
documents supplied with the goods fail to
correspond, immediately inform ABB (either directly,
or through your representative or supplier) and the
haulage contractor that made the delivery.
The cubicles are supplied solely with the accessories
specified at the time of order and validated in the
order confirmation.
The following items are to be found inside the
cubicles:
• instruction manual
• a packet containing screws, nuts, washers,
busbars, etc. for joining the cubicles;
• operating lever
• the shipping documents.
UniSec switchgear must be stored in a dry, dust-free
place with a non-corrosive atmosphere at a
temperature between -25 °C and +70°C, with 95%
relative humidity or less and without condensation.
Please consult us if different requirements are
involved.