62
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
6.6.3.Configuration
This page allows you to set events. When a new device is added the events “Communication failure” and
“Communication restore” are automatically configured in order to monitor the connection status for
that device. If an event occurs, it is shown in the “Diagnostic – Events log” section. An event can occur
after exceeding the selected threshold values (cross-up), after measuring values lower than the selected
threshold values (cross-down) for a determined period (time delay) or if a certain status change (status
change, status change to open, status change to close).
Email notification configuration can be set to following values:
• Cumulative
: the email report is sent X minute (X -configured first period at System setup –
Communication – Email) after the first event occurrence and consists of all events that occurred in this
period. The next report can only be sent after at least Y minutes (Y -configured next period) since the
first alarm occurrence and only in case event conditions are still ongoing
• Dedicated
: the email is sent immediately after each event occurrence
• Both
: cumulative and dedicated options are active
When adding or editing an event, please set the following:
Name
Set the name of the event.
Device type
Select the type of the device.
Device
Select the devices already defined in “My plant - Devices” according
to the Device type selected.
Event type
Type of event: “Cross-up”, “Cross-down”, “Communication failure”
and “Communication restore”.
“Status change”, “Status change to close”, “Status change to open”
only in case of I/O modules or INS-S/H devices.
Category/Measure
Set the specific measure to monitor according to the device
selected.
Threshold
Threshold of selected measure.
Time delay
Define for how long the event criteria should be fulfilled in order to
consider the occurrence as an event.
Alarm
Only when Send event is enabled - If enabled, then event will be
shown in alarms log.
Email notification
If the box is selected, an email will be sent when an event
occurs. The email address has to be defined in “System setup –
Communication - Email”.
Status
Status of configured event, if disabled then event is not active and
won’t be triggered.
The maximum number of events logged for single device per minute is 12, if the value is exceeded
additional event “Events overflow” will be visible in “Events log”
Occurred events are stored in the database, up to 1000 events are stored for single device (if the value is
exceeded, the oldest events will be removed).