![ABB SCU200 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/abb/scu200/scu200_user-manual_3320180024.webp)
24
87
17,5
65
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
3.3.2.Energy meter module
Technical feature
Unit
Description
Supply voltage
[VDC]
Supplied by the InSite modular bus
Connection
InSite modular bus
Power consumption
[W]
0,7
Network type
Three phase + N
Voltage input connection
Screwless terminal block
Voltage specified measurement
range (full accuracy)
[VAC]
80-240 (L1,2,3-N)
Voltage limit range of operation
[VAC]
0 - 277
Frequency
[Hz]
50 / 60
Current transformer supported
secondary side
[mA]
nom.: 0 - 40
max.: 48
Current specified measurement
range (full accuracy)
[mA]
1 - 40
Accuracy (@25 °C, INS-E3 only)
Voltage
0,5%
Current
0,5%
Active power
1%
Apparent power
1%
Reactive power
1%
Power factor
1%
Active Energy
1%
Apparent Energy
1%
Reactive Energy
1%
Conductor cross-section
Solid/fine-stranded conductor
[mm
2
]
0.14…1.5
AWG solid conductor
[AWG]
28-16
AWG fine-stranded conductor
[AWG]
26-14
Fine-stranded conductor with
insulated ferrule
[mm
2
]
0.25 … 0.75
Fine-stranded conductor with
uninsulated ferrule
[mm
2
]
0.25 … 1.5
Strip length
[mm]
8…9
CTS cable length
[m]
0,5
Mounting method
35mm DIN rail (DIN 5022)
Degree of protection
IP20
Dimensions
[mm]
17.5x87.0x64.9 (1M)
Weight
[g]
~52
Oparting temperature
[°C]
-25... +60
Storage temperature
[°C]
-40... +85
Operating altitude
[m]
0… 2000
Standards
IEC61010-1
IEC 61326-1