52
SCU200
INSITE ENERGY MANAGEMENT SYSTEM
• Current sensors
Add
Add and assign new current sensor
Create a new sensor Modbus ID and
then assign it to the physical sensor by
clicking the pushbutton of the sensor
(Note: Wait for confirmation before
assigning the next sensor).
Assign current sensor (already added)
If a sensor ID has already been created
but is unassigned, it is possible to
assign it to the physical sensor by
clicking the pushbutton of the sensor.
Add new current sensor (no assigning) Create a new sensor ID without
assigning it to the physical sensor.
Identify
Clicking the pushbutton of the current sensor allows to display the sensor
Modbus ID number.
Change
MODBUS ID
Select the current Modbus ID number of the current sensor and define the new
Modbus ID number of it.
Remove all
Remove all sensors and their settings. To remove one single sensor, click on the
“X” symbol under the Action column.
• Sensors Definitions
Modbus ID
Sensor identification number.
Name
Defines the name of the sensor.
Phase
Selects the corresponding sensor phase for the calculation of sensor active
power and energy. It is possible to choose: - L1, L2, L3, N, for AC phase to phase
measurements - DC for direct current measurements.
Device
category
Defines the category of the device
Energy
sensors
Defines the flow of energy
Voltage
source
Defines voltage source for DC power and energy calculation. This option can be
configured by clicking on the pen icon. It is possible to set the constant value or
select a register from another device that is already connected.
Power
Factor
source
Defines power factor source for AC power and energy calculation, it allows
to user predefined or external source of power factor. It is possible to set
the constant value or select a register from another device that is already
connected.
[Click a row]
By clicking a row, the row is highlighted in light blue. Additionally, the LED of the selected
sensor will start to blink.
Make sure to select the correct phase on which the current sensor is installed in the phase column. If
needed, change the Power Factor source to a value corresponding to the PF of the measured load.