Type tests according to standards
Table 19. Electromagnetic compatibility
Test
Type test values
Reference standards
1 MHz burst disturbance
2.5 kV
IEC 60255-22-1
100 kHz slow damped oscillatory wave immunity test
2.5 kV
IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz
2-4 kV
IEC 61000-4-12, Class IV
Surge withstand capability test
2.5 kV, oscillatory
4.0 kV, fast transient
IEEE/ANSI C37.90.1
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEC 60255-22-2, Class IV
IEC 61000-4-2, Class IV
Electrostatic discharge
Direct application
Indirect application
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
IEEE/ANSI C37.90.1
Fast transient disturbance
4 kV
IEC 60255-22-4, Class A
Surge immunity test
1-2 kV, 1.2/50
m
s
high energy
IEC 60255-22-5
Power frequency immunity test
150-300 V, 50 Hz
IEC 60255-22-7, Class A
Conducted common mode immunity test
15 Hz-150 kHz
IEC 61000-4-16, Class IV
Power frequency magnetic field test
1000 A/m, 3 s
100 A/m, cont.
IEC 61000-4-8, Class V
Damped oscillatory magnetic field test
100 A/m
IEC 61000-4-10, Class V
Radiated electromagnetic field disturbance
20 V/m, 80-1000 MHz
1.4-2.7 GHz
IEC 60255-22-3
Radiated electromagnetic field disturbance
35 V/m
26-1000 MHz
IEEE/ANSI C37.90.2
Conducted electromagnetic field disturbance
10 V, 0.15-80 MHz
IEC 60255-22-6
Radiated emission
30-1000 MHz
IEC 60255-25
Conducted emission
0.15-30 MHz
IEC 60255-25
Table 20. Insulation
Test
Type test values
Reference standard
Dielectric test
2.0 kV AC, 1 min.
IEC 60255-5
Impulse voltage test
5 kV, 1.2/50
m
s, 0.5 J
Insulation resistance
>100 M
W
at 500 VDC