Table 40. Indications
Function
Value
Buffer capacity
Maximum number of indications presented for single disturbance
96
Maximum number of recorded disturbances
100
Table 41. Event recorder
Function
Value
Buffer capacity
Maximum number of events in disturbance report
150
Maximum number of disturbance reports
100
Resolution
1 ms
Accuracy
Depending on time
synchronizing
Table 42. Trip value recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
30
Maximum number of disturbance reports
100
Table 43. Disturbance recorder
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
ABB
45