Control
Table 29. Autorecloser SMBRREC
Function
Range or value
Accuracy
Number of autoreclosing shots
1 - 5
-
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
(0.000-60.000) s
± 0.5% ± 10 ms
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
(0.00-6000.00) s
Extended autorecloser open time
(0.000-60.000) s
Autorecloser maximum wait time for sync
(0.00-6000.00) s
Maximum trip pulse duration
(0.000-60.000) s
Inhibit reset time
(0.000-60.000) s
Reclaim time
(0.00-6000.00) s
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle
(0.00-6000.00) s
Circuit breaker closing pulse length
(0.000-60.000) s
CB check time before unsuccessful
(0.00-6000.00) s
Wait for master release
(0.00-6000.00) s
Wait time after close command before proceeding to next shot
(0.000-60.000) s
Busbar protection REB670
1MRK505212-BEN E