Monitoring
Table 31. Measurements CVMMXN
Function
Range or value
Accuracy
Frequency
(0.95-1.05) × f
r
±
2.0 mHz
Connected current
(0.2-4.0) × I
r
±
0.5% of I
r
at I
£
I
r
±
0.5% of I at I > I
r
Table 32. Phase current measurement CMMXU
Function
Range or value
Accuracy
Current
(0.1-4.0) × I
r
±
0.2% of I
r
at I ≤ 0.5 × I
r
±
0.2% of I at I > 0.5 × I
r
Phase angle
(0.1–4.0) x I
r
±
0.5° at 0.2 × I
r
< I < 0.5 × I
r
±
0.2° at 0.5 × I
r
≤ I < 4.0 × I
r
Table 33. Phase-phase voltage measurement VMMXU
Function
Range or value
Accuracy
Voltage
(10 to 300) V
±
0.3% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.3° at U ≤ 50 V
±
0.2° at U > 50 V
Table 34. Phase-neutral voltage measurement VNMMXU
Function
Range or value
Accuracy
Voltage
(10 to 300) V
±
0.3% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.3° at U ≤ 50 V
±
0.2° at U > 50 V
Table 35. Current sequence component measurement CMSQI
Function
Range or value
Accuracy
Current positive sequence, I1
Three phase settings
(0.1–4.0) × I
r
±
0.2% of I
r
at I ≤ 0.5 × I
r
±
0.2% of I at I > 0.5 × I
r
Current zero sequence, 3I0
Three phase settings
(0.1–1.0) × I
r
±
0.2% of I
r
at I ≤ 0.5 × I
r
±
0.2% of I at I > 0.5 × I
r
Current negative sequence, I2
Three phase settings
(0.1–1.0) × I
r
±
0.2% of I
r
at I ≤ 0.5 × I
r
±
0.2% of I at I > 0.5 × I
r
Phase angle
(0.1–4.0) × I
r
±
0.5° at 0.2 × I
r
< I < 0.5 × I
r
±
0.2° at 0.5 × I
r
≤ I < 4.0 × I
r
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
ABB
43
Содержание RELION REB670
Страница 1: ...Relion 670 series Busbar protection REB670 Pre configured Product Guide...
Страница 61: ...61...