Table 36. Voltage sequence measurement VMSQI
Function
Range or value
Accuracy
Voltage positive sequence, U1
(10 to 300) V
±
0.3% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage zero sequence, 3U0
(10 to 300) V
±
0.3% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Voltage negative sequence, U2
(10 to 300) V
±
0.3% of U at U ≤ 50 V
±
0.2% of U at U > 50 V
Phase angle
(10 to 300) V
±
0.3° at U ≤ 50 V
±
0.2° at U > 50 V
Table 37. Event counter CNTGGIO
Function
Range or value
Accuracy
Counter value
0-100000
-
Max. count up speed
10 pulses/s (50% duty cycle)
-
Table 38. Disturbance report DRPRDRE
Function
Range or value
Accuracy
Pre-fault time
(0.05–9.90) s
-
Post-fault time
(0.1–10.0) s
-
Limit time
(0.5–10.0) s
-
Maximum number of recordings
100, first in - first out
-
Time tagging resolution
1 ms
See table
Maximum number of analog inputs
30 + 10 (ex internally
derived)
-
Maximum number of binary inputs
96
-
Maximum number of phasors in the Trip Value recorder per recording
30
-
Maximum number of indications in a disturbance report
96
-
Maximum number of events in the Event recording per recording
150
-
Maximum number of events in the Event list
1000, first in - first out
-
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
Table 39. Event list
Function
Value
Buffer capacity
Maximum number of events in the list
1000
Resolution
1 ms
Accuracy
Depending on time synchronizing
Busbar protection REB670