Current protection
Table 25. Four step phase overcurrent protection OC4PTOC
Function
Setting range
Accuracy
Operate current
(5-2500)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Reset ratio
> 95% at (50–2500)% of
lBase
-
Min. operating current
(1-10000)% of
lBase
±
1.0% of I
r
at I ≤ I
r
±
1.0% of I at I > I
r
Relay characteristic angle (RCA)
(40.0–65.0) degrees
±
2.0 degrees
Relay operating angle (ROA)
(40.0–89.0) degrees
±
2.0 degrees
2nd harmonic blocking
(5–100)% of fundamental
±
2.0% of I
r
Independent time delay at 0 to 2 x
I
set
(0.000-60.000) s
±
0.2 % or
±
35 ms whichever is
greater
Minimum operate time
(0.000-60.000) s
± 2.0 % or ± 40 ms whichever is
greater
Inverse characteristics, see
table
16 curve types
See table
Operate time, start non-directional
at 0 to 2 x I
set
Min. = 15 ms
Max. = 30 ms
Reset time, start non-directional at
2 to 0 x I
set
Min. = 15 ms
Max. = 30 ms
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Table 26. Four step single phase overcurrent protection PH4SPTOC
Function
Setting range
Accuracy
Operate current
(1-2500)% of l
base
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Second harmonic blocking
(5–100)% of fundamental
±
2.0% of I
r
Independent time delay
(0.000-60.000) s
±
0.5%
±
10 ms
Minimum operate time
(0.000-60.000) s
±
0.5%
±
10 ms
Inverse characteristics, see
table
19 curve types
Operate time, start function
25 ms typically at 0 to 2 x I
set
-
Reset time, start function
25 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-