Station communication
Table 44. IEC 61850-8-1 communication protocol
Function
Value
Protocol
IEC 61850-8-1
Communication speed for the IEDs
100BASE-FX
Protocol
IEC 608–5–103
Communication speed for the IEDs
9600 or 19200 Bd
Protocol
DNP3.0
Communication speed for the IEDs
300–19200 Bd
Protocol
TCP/IP, Ethernet
Communication speed for the IEDs
100 Mbit/s
Table 45. LON communication protocol
Function
Value
Protocol
LON
Communication speed
1.25 Mbit/s
Table 46. SPA communication protocol
Function
Value
Protocol
SPA
Communication speed
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
Slave number
1 to 899
Table 47. IEC60870-5-103 communication protocol
Function
Value
Protocol
IEC 60870-5-103
Communication speed
9600, 19200 Bd
Table 48. SLM – LON port
Quantity
Range or value
Optical connector
Glass fibre: type ST
Plastic fibre: type HFBR snap-in
Fibre, optical budget
Glass fibre: 11 dB (1000 m typically *)
Plastic fibre: 7 dB (10 m typically *)
Fibre diameter
Glass fibre: 62.5/125
m
m
Plastic fibre: 1 mm
*) depending on optical budget calculation
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
46
ABB
Содержание RELION REB670
Страница 1: ...Relion 670 series Busbar protection REB670 Pre configured Product Guide...
Страница 61: ...61...