Differential protection
Table 24. Busbar differential protection
Function
Range or value
Accuracy
Operating characteristic
S=0.53 fixed
±
2.0% of I
r
for I
<
I
r
±
2.0% of I for I > I
r
Reset ratio
> 95%
-
Differential current operating level (1-100000) A
±
2.0% of I
r
for I
<
I
r
±
2.0% of I for I > I
r
Sensitive differential operation
level
(1-100000) A
± 2.0% of I
r
for I < I
r
± 2.0% of I for I < I
r
Check zone operation level
(0-100000) A
±
2.0% of I
r
for I
<
I
r
±
2.0% of I for I > I
r
Check zone slope
(0.0-0.9)
-
Timers
(0.000-60.000) s
±
0.5%
±
10 ms
Timers
(0.00-6000.00) s
±
0.5%
±
10 ms
Operate time
19 ms typically at 0 to 2 x I
d
12 ms typically at 0 to 10 x I
d
-
Reset time
21 ms typically at 2 to 0 x I
d
29 ms typically at 10 to 0 x I
d
-
Critical impulse time
8 ms typically at 0 to 2 x I
d
-
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2