Basic IED functions
IEC 61850
Function description
Basic functions included in all products
IntErrorSig
Self supervision with internal event list
1
TIME
Time and synchronization error
1
TimeSynch
Time synchronization
1
ActiveGroup
Parameter setting groups
1
Test
Test mode functionality
1
ChangeLock
Change lock function
1
TerminalID
IED identifiers
1
Productinfo
Product information
1
MiscBaseCommon
Misc Base Common
1
IEDRuntimeComp
IED Runtime Comp
1
RatedFreq
Rated system frequency
1
SMBI
Signal Matrix for binary inputs
40
SMBO
Signal Matrix for binary outputs
40
SMMI
Signal Matrix for mA inputs
4
SMAI
Signal Matrix for analog inputs
24
Sum3Ph
Summation block 3 phase
12
LocalHMI
Parameter setting function for HMI in PCM600
1
LocalHMI
Local HMI signals
1
AuthStatus
Authority status
1
AuthorityCheck
Authority check
1
AccessFTP
FTP access with password
1
SPACommMap
SPA communication mapping
1
DOSFRNT
Denial of service, frame rate control for front port
1
DOSOEMAB
Denial of service, frame rate control for OEM port AB
1
DOSOEMCD
Denial of service, frame rate control for OEM port CD
1
3. Differential protection
The function consists of differential protection algorithm,
sensitive differential protection algorithm, check zone
algorithm, open CT algorithm and two supervision algorithms.
Busbar differential protection
This protection function is intended for fast and selective
tripping of faults within protected zone. For each current
input, the CT ratio can be set from the front HMI or via the
parameter-setting tool, PCM600. In this way adaptation to
different CT ratios is provided in the simplest way. The
minimum pick-up value for the differential current is then set
to give a suitable sensitivity for all internal faults. This setting
is made directly in primary amperes. For busbar protection
applications typical setting value for the minimum differential
operating current is from 50% to 150% of the biggest CT.
The settings can be changed from the front HMI or via the
parameter-setting tool, PCM600.
All current inputs are indirectly provided with a restraint
feature. The operation is based on the well-proven RADSS
percentage restraint stabilization principle, with an extra
stabilization feature to stabilize for very heavy CT saturation.
Stability for external faults is guaranteed if a CT is not
Busbar protection REB670
1MRK505212-BEN E
Pre-configured
Product version: 1.2
12