5.1.7.2
Validation on demand
The validity of an application configuration can be checked by clicking
Validate
Configuration
in the toolbar. The Application Configuration tool checks the
application configuration for formal correctness. The found problems are divided into
warnings and errors.
•
Warnings, marked with a yellow warning icon
•
Example: a variable connected to an output signal that is not connected
•
Example: if an output from a higher execution order function is connected
to inputs of lower execution order function
•
Errors, marked with a red circle with a cross
•
Example: unconnected hardware output
Warnings do not prevent writing to the protection relay. However, errors must be
corrected before writing the application configuration to the protection relay. The
application configuration can be saved and the Application Configuration tool can be
closed with open errors, but the application configuration cannot be written to the
protection relay.
These problems are listed in the
Output
view under the
Application Configuration
tab. Double-clicking the error or warning row navigates to the
MainApplication/
Page/Area
, where the problem was identified.
IEC09000614_2_en.vsd
IEC09000614 V2 EN
Figure 41:
ACT: Validation on demand
1MRS756800 F
Section 5
Protection and control engineering
630 series
63
Engineering Manual