Figure 96:
Semi-automatic configuring of RCB clients
1.
Configure the default clients which are used by the rule-based RCB generation
to automatically configure RCB clients.
Use buttons on the RCB client editor.
•
Clear All
removes all default clients
•
Configure Empty
fills out only default clients for those IEDs that have no
clients configured yet
•
Configure All
deletes all existing default clients and fills them out
afterwards
2.
Configure the RCBs clients.
The default clients must be configured before configuring RCB clients
otherwise the automatic RCB client configuration does not work. Use buttons on
the RCB client editor.
•
Clear All
removes all RCB clients
•
Configure Empty
copies the default client configuration of this IED to its
RCBs (only for those RCBs that have no clients configured yet)
•
Configure All
deletes the existing RCB clients and copies the default
client configuration of this IED to its RCBs
IET600 updates the
Enabled Clients
configuration value of the RCBs
automatically based on the configuration made in the RCB client
editor. In addition, IET600 always reserves one extra engineering
client. For example, when configuring three RCB clients, the
Enabled
Clients
value of that RCB is “4”.
Section 7
1MRS756800 F
IEC 61850 communication engineering
124
630 series
Engineering Manual